IG541 Fire Extinguishing Systems
Promulgator: :管理员 Send date: :2015-05-14 15:17 Visitor: :What is INERGEN fire suppression system?
Inergen fire suppression is a blend of naturally occurring gases; Nitrogen, Argon, & a small amount of carbon dioxide. The Inergen is made up of all these gas with a blend mix consisting of Argon 52%,Nitrogen 40% and CO2 8%.
The benefits
INERGEN is a highly effective fire suppression system for extinguishing fire & preventing re-ignition with no risk to people or damage to equipment if engineered and installed by a qualified fire suppression systems installation company.
The INERGEN fire suppression also has no adverse affect on the ozone layer as it is completely made up of naturally occurring gases.
INERGEN fire suppression systems also have a zero global warming potential, & no atmospheric lifetime
An INERGEN system is certified as a safe and clean fire suppression system for occupied spaces
Medically evaluated by leading authorities around the world, the blend of INERT gases maintains normal blood-oxygen levels, thereby ensuring heart rate & mental performance remain optimal to ensure a safe escape during or after a fire suppression system discharge.
Unlike many other suppression systems which need to be located close to the protected area, INERGEN can be stored up to further away, & as it is organic in structure it is not subject to time use limiting restrictions.
INERGEN fire suppression is stored & discharged as a gas, when the fire suppression system discharges the INERGEN gas, it is clear, insuring a safe & visually un-obscured exit.
Suitable Environments for and INERGEN fire suppression system
Laboratories/ Telecommunication Rooms/ Compter & Server Environments/ Contro Rooms/ Archives etc.
Technology Parameters:
Model No.
QMH15/70
QMH15/80
QMH15/90
QMH15/105
Executive Standard
GB25972-2010
Design Working Pressure (20℃)
15.0Mpa
Storage Cylinder Volume
70L
80L
90L
105L
IG541 Filling Volume
10.3 m³
11.8 m³
13.3 m³
15.5 m³
Agent Extinguishing Time
≤60S
Driver N2 Filling Pressure (20℃)
6.0Mpa
Working Power
Main Power: 220V/50Hz
Standby Power: DC24V/3A
Power Dissipation
When Hint: ≤60W
When Operation: ≤60W
Environment Conditions
Environment Temp.:0-50℃
Relative Humidity: 93±3%
Activation Method
Electrical, Automatic Manual, Emergency Mechanical
Extinguishing Time Delay
0-30s adjustable