JiangXi Tsinghua Industrial Co.,Ltd
Tel:86-0790-6427119
Fax:86-0790-6450738
www.jtifire.com
- FM200 Systems
-
Double Cylinder Non-pipeline FM200 Fire Extinguishing System
Promulgator: :管理员 Send date: :2015-05-14 09:21 Visitor: :What is FM200?
FM200 is a Clean Gas Fire Extinguishing agent mainly with chemical fire extinguishing and with physical fire extinguishing; Colorless, odorless, non-toxicity, non-conductive, no secondary pollution, non corrosive, no damage to precision instrument and electronic equipment.
ODP=0 and meet the requirement of environment protection, and no corrosive no residue no grease after extinguishing, and can be vented by normal venting channels, is halon 1301 and 1211 alternative products.
It is the most clean fire extinguishing agent and with characteristic of clean, non toxicity, non conductive and high efficiency in fire extinguishing.
FM200 with NOAEL Value of 9%, where other normal similar fire extinguishing agent is 10%, and so our FM200 have no damage to human body.
This automatic FM200 fire extinguishing systems suitable for all workplace, like computer rooms, communication facilities, transformer rooms, Library and archive rooms, flammable liquids products, cable wells, machinery etc.
1.Characteristics
Use new materials for key parts and our FM200 is with stable performance and main performance index above domestic advanced technology levels, stable in operation and easy to maintenance,; and at the same time with manual activation and automatic activation etc many operation optional; it is high efficiency in fire extinguishing, high speed in fire extinguishing, non toxicity, non conductive, non corrosive, no residue, no damage to precision instrument and electronic equipments. Environment friendly with ODP=0. halon-alternative.
It’s control parts can be connected with the fire control center and also can separately connect with gas fire control panel only, very convenience and flexible for people and fire fighters etc.
2.Applications
1.fire fire class A,B,C,E and can be suitable for all place with people.
2.The workplace have requirement of without residue after extinguishing.
3.Have valuable articles, Precious archives and hardware and software etc.
4.Special for computer rooms, cabinets, server rooms, telecom control room, airport control room, bank coffers, library, museum and Archives etc.
Type
Fixed Type
Filling Pressure
2.5Mpa
FM200 Storage Cylinder
Single Cylinder: 70L,90L,120L,150L
Double Cylinder: 40L,90L,120L,150L
Working Temperature
-10℃-+50℃
Power
Main Power Supply
220V-50Hz
Stand-by Power Supply
DC24V
Activation Type
Electrical Activation
DC20V-28V
Pneumatic Activation
Emergency Mechanical Start
Mechanical Operation:≤150N
Activation Delay
0-30s adjustable
Activation Pneumatic Power
Gas in use
Working Pressure
Extinguishing Time
≤10S
Max. Protection Area
500 m³
Max. Protection Volume
1600 m³
Protection Environment Temp.
>-10℃
One Cylinder Group Type
Double Cylinder Group Type
QGG70/2.5-QH
QGG40/2.5*2-QH
QGG90/2.5-QH
QGG90/2.5*2-QH
QGG120/2.5-QH
QGG120/2.5*2-QH
QGG150/2.5-QH
QGG150/2.5*2-QH